AVR TYPE HWR6O-5 | Range 1 | Range 2 | ||
Input voltage | 95-132v | 190-264v | ||
Frequency | 50/60Hz | 50/60Hz | ||
Output Voltage | ||||
Voltage max for field forcing during load change | 45v DC @ 12OvAC input | 90v DC @ 240v AC input | ||
Recommended max FL. voltage | 30v DC @ 120v AC input | 60v DC @ 240v AC input | ||
Output Current DC Continuous | 5A | 5A | ||
Field Resistance | 6 ohms min - 100 ohms max @ 120v AC input | 12 ohms min - 100 ohms max @ 240v AC input |
AVR TYPE HWR6O-10 | Range 1 | Range 2 | ||
Input voltage | 95-132v | 190-264v | ||
Frequency | 50/60Hz | 50/60Hz | ||
Output Voltage | ||||
Voltage max for field forcing during load change | 45v DC @ 12OvAC input | 90v DC @ 240v AC input | ||
Recommended max FL. voltage | 30v DC @ 120v AC input | 60v DC @ 240v AC input | ||
Output Current DC Continuous | 10A | 10A | ||
Field Resistance | 3 ohms min - 100 ohms max @ 120v AC input | 6 ohms min - 100 ohms max @ 240v AC input |
AVR TYPE FWR12O-5 | Range 1 | Range 2 | ||
Input voltage | 95-132v | 190-264v | ||
Frequency | 50/60Hz | 50/60Hz | ||
Output Voltage | ||||
Voltage max for field forcing during load change | 90v DC @ 12OvAC input | 180v DC @ 240v AC input | ||
Recommended max FL. voltage | 60v DC @ 120v AC input | 120v DC @ 240v AC input | ||
Output Current DC Continuous | 5A | 5A | ||
Field Resistance | 12 ohms min - 100 ohms max @ 120v AC input | 24 ohms min - 100 ohms max @ 240v AC input |
AVR TYPE FWR12O-1O | Range 1 | Range 2 | ||
Input voltage | 95-132v | 190-264v | ||
Frequency | 50/60Hz | 50/60Hz | ||
Output Voltage | ||||
Voltage max for field forcing during load change | 90v DC @ 12OvAC input | 180v DC @ 240v AC input | ||
Recommended max FL. voltage | 60v DC @ 120v AC input | 120v DC @ 240v AC input | ||
Output Current DC Continuous | 10A | 10A | ||
Field Resistance | 6 ohms min - 100 ohms max @ 120v AC input | 12 ohms min - 100 ohms max @ 240v AC input |